Fujitsu Fault Codes: Count the Flashes, Then Find Your Code

Reading time 20 minUpdated 25 Nov 2026For Australian homesBy Checked against sources by our review team, 25 Nov 2026
Short answer

Fujitsu wall splits show fault codes as blinking lamps, and wired controllers show them on screen. Count the flashes, use the decoder table from General’s installation manual, rule out normal lamp messages, and know when to stop and call a licensed technician.

On a wall split run from a handheld remote, Fujitsu fault codes are not printed on a screen. Instead, the indoor unit blinks its lamps in a pattern, and you turn those blinks into a code. On a system with a wired wall controller, the code appears on the controller display instead. This guide decodes both, then shows what you can check and when to call a licensed technician.

Every code meaning and lamp pattern below comes from General’s own Australian manuals, and the safety rules come from the government pages named in that section. The code table comes from one wall split range, so other models can differ. Where a code could not be confirmed, it is left out rather than guessed.

How do I get the fault code on my Fujitsu remote or unit?

What you use to run the system decides where the code shows up.

Path one: a wall split with a handheld remote

The handheld remote does not display fault codes. Instead, the code appears on the indicator lamps of the indoor unit. The ASTG09KMTC and ASTG12KMTC indoor installation manual on General’s Australian support site says this directly. With a wireless remote, the lamp panel outputs error codes as blinking patterns.

The panel on these models has an Operation lamp in green, a Timer lamp in orange and an Economy lamp in green. When a fault code is showing, the Operation and Timer lamps blink slowly while the Economy lamp flickers fast. The manual gives the timing as 0.5 seconds on and 0.5 seconds off for a slow blink, and 0.1 seconds on and 0.1 seconds off for the fast flicker.

Path two: a wired wall controller

If your system has a controller fixed to the wall, the same installation manual says error codes appear on the remote control display. A wall split can have one as an option, and General’s support page for its ARTH ducted range lists those units with the UTY-RNRYT5 wired controller. In that case you read the code from the screen, so there is nothing to count. Skip ahead to the section on wired controllers below.

Count before you switch anything off

The installation manual notes that an error display is shown only during operation. So record the pattern before you touch the remote or the breaker.

  1. Stand where the lamp panel is easy to see. Close a blind if sun is washing out the small lights.
  2. Film the panel on your phone for at least two full cycles. A cycle ends with a pause, then the pattern starts again.
  3. Play the video back slowly and count the green Operation blinks.
  4. Next, count the orange Timer blinks in the same cycle.
  5. Check that the Economy lamp is flickering fast. That confirms you are looking at an error display rather than a normal lamp message.
  6. Write down both counts, plus what the unit was doing when it stopped.

A single missed blink changes the code. Four green and one orange is a room sensor error, while four green and two orange is a coil sensor error.

What do the flashing lights on a Fujitsu air conditioner mean?

Not every blink is a fault. The quickest test is the Economy lamp. If it is not flickering fast, you are probably looking at one of the normal messages below.

Lamp messages that are not faults

These come from General’s operating manual for the ASTG18KMTC, ASTG22KMTC and ASTG24KMTC wall splits.

  • Operation lamp blinking in heating. The automatic defrost is running. The manual says the indoor unit can stop for up to 15 minutes while it melts frost off the outdoor coil. Steam or water from the outdoor unit during defrost is also normal. If heating does not return afterwards, see the guide on Fujitsu heat mode not working.
  • Timer lamp blinking after a blackout. A power interruption reset the internal clock, so any timer you set has lost its countdown. The manual says to set the clock and the timer again.
  • Lamps blinking with a beep when you press a remote button. If a wired controller is also connected, some wireless remote functions are restricted. The manual lists the weekly timer, Powerful, Outdoor Unit Low Noise and 10 °C Heat. Choosing one of these makes the unit beep and blink its lamps.

Reminder and supplier signals

  • The filter indicator sign. This cleaning reminder works only if it was set during installation. The manual says the Economy lamp then blinks 3 times at intervals of 21 seconds. That is slow and spaced out, unlike the constant fast flicker of an error display. It is reset with a press of two seconds or less on the Manual Auto button while the unit is stopped.
  • Demand response blinking. This function needs a separate arrangement with your electricity supplier. While the supplier runs demand response mode, the manual says the Operation lamp blinks twice in its pattern, and performance may drop or the unit may stop.

A Fujitsu timer light flashing on its own can simply be the clock message rather than a breakdown. It becomes a fault code only when the Operation lamp is also counting and the Economy lamp is flickering fast.

Flash-to-code decoder table

This table comes from one wall split range, the ASTG09KMTC and ASTG12KMTC, and repeats the error display table in its installation manual. The manual warns that it also lists errors that do not apply to that product. Other ranges, older models and ducted systems can use different codes or meanings, so check the manual for your own model.

Codes with their own section below are linked. Letters are shown as larger counts. For example, A is ten Operation blinks and J is thirteen.

Codes 11 to 5U

Operation blinks (green)Timer blinks (orange)CodeManual description
1111Serial communication error
1212Wired remote controller communication error, or server room control communication error
1515Check run unfinished, or automatic airflow adjustment error
1616Peripheral unit transmission PCB connection error
1818External communication error
2121Unit number or refrigerant circuit address setting error (Simultaneous Multi)
2222Indoor unit capacity error
2323Combination error
2424Connection unit number error (Simultaneous Multi and Flexible Multi)
2626Indoor unit address setting error
2727Primary unit, secondary unit setup error (Simultaneous Multi)
2929Connection unit number error in wired remote controller system
3131Power supply interruption error
3232Indoor unit PCB model information error
3333Indoor unit motor electricity consumption detection error
3535Manual auto switch error
3939Indoor unit power supply error for fan motor
3103AIndoor unit communication circuit (wired remote controller) error
4141Room temperature sensor error
4242Indoor unit heat exchanger middle temperature sensor error
4444Human sensor error
5151Indoor unit fan motor error
5353Drain pump error
5454Electric air cleaner reverse VDD error
5555Filter set error
5757Damper error
5858Intake grille error
5959Indoor unit fan motor 2 error (left side fan)
5105AIndoor unit fan motor 3 error (right side fan)
5155UIndoor unit error

Codes 61 to J2

Operation blinks (green)Timer blinks (orange)CodeManual description
6161Outdoor unit reverse or missing phase and wiring error
6262Outdoor unit main PCB model information error or communication error
6363Inverter error
6464Active filter error, PFC circuit error
6565Trip terminal L error
6868Outdoor unit rush current limiting resistor temperature rise error
6106ADisplay PCB microcomputers communication error
7171Discharge temperature sensor error
7272Compressor temperature sensor error
7373Outdoor unit heat exchanger liquid temperature sensor error
7474Outdoor temperature sensor error
7575Suction gas temperature sensor error
76762 way valve or 3 way valve temperature sensor error
7777Heat sink temperature sensor error
8282Sub-cool heat exchanger gas inlet or outlet temperature sensor error
8383Liquid pipe temperature sensor error
8484Current sensor error
8686Discharge pressure sensor, suction pressure sensor or high pressure switch error
9494Trip detection
9595Compressor rotor position detection error (permanent stop)
9797Outdoor unit fan motor 1 error
9898Outdoor unit fan motor 2 error
99994 way valve error
9109ACoil (expansion valve) error
101A1Discharge temperature error
103A3Compressor temperature error
104A4High pressure error
105A5Low pressure error
132J2Branch boxes error (Flexible Multi)

In every row, the Economy lamp flickers fast while the other two count. If you count ten or more green blinks, you are in the letter codes, so a video matters even more there.

Fujitsu split system fault codes

The sections below expand the Fujitsu error codes that wall split owners search for. The meanings come from the ASTG09KMTC and ASTG12KMTC installation manual. The owner checks come from the ASTG18KMTC, ASTG22KMTC and ASTG24KMTC operating manual.

One rule covers every code. The operating manual says that when the Operation and Timer lamps blink while the Economy lamp flickers fast, you should stop the unit, turn off its circuit breaker and consult service personnel. The checks below are things to note or tidy with the unit off, never with a cover open.

What does Fujitsu error code 11 mean?

The table calls code 11 a serial communication error. The indoor and outdoor units exchange signals over their connecting cable, and this code means that exchange has failed. On the lamps it is one green blink and one orange blink, which can look like a simple flicker. The fast Economy lamp is your clue that it is a code.

Worth noting: whether the fault followed a blackout, a storm or recent work at the switchboard. The operating manual also says nearby electrical appliances or a radio transmitter can cause a malfunction. A cable fault or board fault needs live testing between the two units, so this is technician work.

Code 12: wired remote controller communication error

Code 12 means the indoor unit has lost contact with a wired controller. The same table row also covers a server room control communication error. It is one green blink and two orange.

A flat battery in a handheld remote does not cause code 12. That is a separate problem, and the operating manual’s checklist simply suggests replacing the batteries. Code 12 concerns the cable and controller on the wall. The controller wiring connects to the indoor unit’s electrics, so leave it alone.

Code 32: indoor unit PCB model information error

Three green and two orange. PCB means printed circuit board. The table says the indoor board has a problem with its model information. This is an electronics fault inside the indoor unit, with nothing for an owner to check beyond noting when it started.

What does Fujitsu error code 41 mean?

Fujitsu error code 41 is a room temperature sensor error. It shows as four green blinks and one orange. Without this reading, the unit cannot control the room.

Code 41 is different from a room that simply feels warm. The operating manual lists ordinary reasons for poor cooling or heating, such as a blocked intake grille or outlet, an open window or door, or the fan set to Quiet. Those do not create a code. If code 41 is showing, the sensor or its connection needs testing inside the unit.

Code 42: indoor heat exchanger middle temperature sensor error

Four green and two orange. The heat exchanger is the indoor coil behind the filter. Code 42 means the sensor on that coil is not reporting properly.

Ice on the coil is a separate issue. The operating manual notes that the heat exchanger may freeze in Cooling or Dry mode, depending on conditions, and cause water leakage. Freezing does not need a code to happen. If code 42 is showing, the sensor itself needs checking.

Code 51: indoor unit fan motor error

Five green and one orange. Before assuming a fault, remember the manual lists normal slow fan behaviour. The fan turns very slowly at the start of heating while the unit warms up. The indoor unit also stops for up to 15 minutes during defrost, and in Dry mode it runs at low fan speed and may stop from time to time.

Those normal states do not flicker the Economy lamp. The fan sits behind the front panel, so checking it is technician work.

Code 53: drain pump error

Five green and three orange. This code concerns a drain pump, so it only applies to units that have one. Check your own manual to see whether your model uses a pump or a gravity drain hose. The operating manual lists water leaking from the unit as a reason to stop, turn off the breaker and consult service personnel.

Code 61: outdoor unit reverse or missing phase and wiring error

Six green and one orange. The table links this code to the power supply phases and wiring at the outdoor unit. That is the incoming electrical supply, which only a licensed electrician or technician should test.

Code 62: outdoor unit main PCB model information or communication error

Six green and two orange. This is the outdoor main board reporting either a model information problem or a communication fault. Several codes share six green blinks, so the orange count is what separates them.

What does Fujitsu error code 63 mean?

Fujitsu error code 63 is listed in the table simply as an inverter error. It is six green blinks and three orange. In an inverter system, electronics in the outdoor unit vary the compressor speed, and those parts carry high voltage.

A quiet outdoor unit on its own is not proof of code 63. The operating manual explains that after power is switched from off to on, the compressor will not run for about 3 minutes. In heating, the outdoor unit also stops when the room is already warmer than the set temperature. If the six and three pattern is showing, however, stop the unit.

Code 64: active filter error, PFC circuit error

Six green and four orange. PFC stands for power factor correction, a circuit in the unit’s power electronics. Note any recent switchboard changes, storms or flickering power, because those details help a technician. Testing the supply or the circuit is electrical work.

Code 65: trip terminal L error

Six green and five orange. The table gives no more detail than the name. Treat it as a stop code.

Code 71: discharge temperature sensor error

Seven green and one orange. The discharge sensor reads the temperature of the pipe leaving the compressor. Code 71 means the sensor reading itself has failed. It is easy to confuse with A1, which the table lists separately as a discharge temperature error. In short, 71 points at the sensor, while A1 points at the temperature it measures.

Code 74: outdoor temperature sensor error

Seven green and four orange. This sensor reads the air at the outdoor unit. A missed orange blink here could make it look like code 73, the outdoor heat exchanger liquid temperature sensor. So count the orange run twice.

Cold weather produces several normal outdoor behaviours that are not code 74. The operating manual lists defrost pauses, steam during defrost and water draining from the outdoor unit. None of these flicker the Economy lamp.

Code 84: current sensor error

Eight green and four orange. The table describes this as a current sensor error in the electronics. Nothing here is owner serviceable.

Code 94: trip detection

Nine green and four orange. The table gives no more detail than the name. Nine is a long count, and 95, 97, 98, 99 and 9A also start with nine green blinks. Watch at least two cycles.

The one useful owner check is airflow. The operating manual says to keep the surroundings of the outdoor unit clean and tidy, and not to place items around it. It warns that objects blocking or entering the outlet ports may cause a malfunction. With the unit off, move stored items, bins and pot plants away, and clear leaves from the outside of the casing. Do not reach through the grille.

Code 95: compressor rotor position detection error (permanent stop)

Nine green and five orange. The table marks this code as a permanent stop. In other words, the unit is designed to stay off after this fault, so leave it off and arrange a technician.

Code 97: outdoor unit fan motor 1 error

Nine green and seven orange. The outdoor fan moves air through the outdoor coil. With the unit stopped and the breaker off, you can look at the fan grille from outside for leaves, plastic or nests. Do not put hands or tools through the grille. If something is caught inside, leave the breaker off.

Code 99: 4 way valve error

Nine green and nine orange. The 4 way valve switches a reverse cycle system between cooling and heating. It sits in the sealed refrigerant circuit, so this is a licensed refrigeration job.

Code A1: discharge temperature error

Ten green and one orange. The table lists it as a discharge temperature error. The table lists it separately from the sensor error, code 71, and gives no cause. Diagnosis is technician work.

Code A3: compressor temperature error

Ten green and three orange. The table lists this as a compressor temperature error, separate from code 72, which is the compressor temperature sensor. Again, a stop code.

Code A4: high pressure error

Ten green and four orange. Pressure faults concern the refrigerant circuit directly. Never loosen fittings or caps on the outdoor unit to investigate.

Code A5: low pressure error

Ten green and five orange. The table lists it beside the high pressure error. Diagnosis belongs to a licensed technician with refrigeration gauges.

How do Fujitsu ducted error codes and wired controllers differ?

Fujitsu ducted error codes are read from a wired controller, not from lamps. General’s support page for the ARTH ducted range pairs those units with the UTY-RNRYT5 wired controller and attaches its installation manual. The ASTG installation manual confirms only that a wired controller shows the code on its display. The operating manual adds that the appearance and steps of an optional controller may differ, and points you to that controller’s own operating manual. General publishes a separate manual for each controller model.

Several rows in the table relate directly to wired controller systems. They are code 12, code 29 for a connection unit number error in a wired remote controller system, and code 3A for an indoor unit communication circuit error on the wired controller side. If any of these appears, check whether the controller display is still responding, and note it for the technician.

Codes with a dot or more characters

Some owners see a code with a dot, for example Fujitsu error code 11.1. The KMTC table only uses two-character codes. So a dotted code should be looked up in the manual for the controller printed on your wall unit, rather than read as code 11 by guesswork. The same goes for any code not in the table above.

Are there separate Fujitsu multi split fault codes?

The installation manual does not have a separate multi split table. Instead, its shared table tags certain rows with the system type they belong to. Codes 21 and 27 are marked Simultaneous Multi. Code 24 appears in both a Simultaneous Multi and a Flexible Multi form. Code J2, thirteen green and two orange, is a branch boxes error for Flexible Multi systems.

Several of these are described as setting or address errors, which concern how the system was configured. The installer or a licensed technician is the right contact.

How do I reset a Fujitsu fault code?

The operating manual does not give owners a reset procedure for a fault code. What it says instead is clear. When the error display appears, stop the unit, turn off the electrical breaker and consult service personnel. Here is how to follow that safely.

  1. Record the code first. Film the lamps or photograph the controller screen. The display shows only while the unit is operating.
  2. Stop the unit with the remote or controller. The manual warns against starting or stopping the unit by pulling the plug or switching the power at the breaker, so use the remote first.
  3. Then turn off the air conditioner’s circuit breaker. The manual also notes that the unit is not isolated from the power supply while it remains connected, even when stopped.
  4. Do the outside checks while the power is off. Clear items and debris from around the outdoor unit, and check that nothing blocks the indoor intake grille or outlet.

The manual does describe one situation where switching the breaker off and on is the answer. If nearby electrical appliances or a radio transmitter cause a malfunction, it says to turn off the circuit breaker once, turn it on again, and resume with the remote. After a restore, expect a delay of about 3 minutes before the compressor runs.

That restart is for interference only. For an error display, the manual gives no restart step, so do not restart the unit to clear the code. Leave the breaker off and consult service personnel, as the manual says. Keep your recording, because it shows the technician exactly what the unit reported.

Which Fujitsu fault codes need a licensed technician?

The manual’s rule covers every code in the table: stop the unit, turn off the breaker and consult service personnel. Some codes carry extra risk:

  • Power and electronics codes in the sixties, such as 61, 62, 63, 64 and 65.
  • Codes that point at the sealed refrigerant circuit, such as 99, A1, A3, A4 and A5.
  • Code 95, which the table marks as a permanent stop.
  • A burning smell, smoke or water leaking from the unit. The operating manual lists each of these as a reason to stop immediately, turn off the breaker and consult service personnel.
  • A breaker that trips again after you reset it.

Two pieces of Australian law sit behind this. Refrigerant work is licensed under the Ozone Protection and Synthetic Greenhouse Gas Management Act 1989, which requires a refrigerant handling licence for installing, servicing and maintaining air conditioning equipment. Electrical work is also regulated. Energy Safe Victoria says unqualified electrical work is extremely dangerous and illegal, and other states have their own regulators.

So never open the outdoor unit, remove the indoor front panel beyond the filter, touch circuit boards or capacitors, or loosen pipe joints. If you want to know what a visit usually involves, read what an air conditioner repair involves.

What to have ready for the technician

  • The lamp counts or controller code, plus your video.
  • The indoor and outdoor model numbers from the rating labels on each unit.
  • When the code first appeared, and what the unit was doing.
  • Any recent blackout, storm, switchboard work or solar install.

Where can I find the official Fujitsu error code list?

The fullest Fujitsu error code list for a wall split sits in its installation manual, not the operating manual. General’s Australian support site, assist.generalairstage.com.au, has a page for each model with the indoor and outdoor installation manuals attached. Search it using the model number from the rating label on your unit.

Remember the caution printed with the table. It contains errors that do not apply to every product. A code that appears in it is not proof your model can show that code.

Why the website says General, not Fujitsu

Fujitsu air conditioner error codes are now published under the General name in Australia. The old address, fujitsugeneral.com.au, now redirects to generalairstage.com.au. The support portal names itself General Airstage Australia. Older manuals still name Fujitsu General (Aust.) Pty Limited. For model history and where to find each manual, see the Fujitsu and General owner guide.

If the unit runs but behaves oddly without showing a code, the Fujitsu troubleshooting by symptom guide covers that side. For other makes, the fault codes for other brands index lists each brand’s guide.

What should I do when my Fujitsu shows a code?

Fujitsu error codes come in two forms: lamp blinks on a wall split with a handheld remote, or a code on a wired controller screen. Rule out normal messages such as defrost first. Then decode, stop the unit, switch off the breaker as the manual directs, and leave anything inside the units to a licensed technician.