Bonaire heaters report faults on the Navigator screen, on a Slimline control or as flashes on the heater board. Find your controller, read the error log, compare the number with Bonaire’s own MB3, MB4 and MB5 lists, clear it once and know which codes need a licensed gasfitter.
Bonaire Navigator error codes appear when a Bonaire ducted gas heater stops itself and reports why. The catch is that a Bonaire heater can report a fault in three different places. A Navigator controller shows CO or ERROR on its screen and keeps a log of numbered faults. By comparison, a Slimline wall control shows Er. Every heater also flashes a status light on its control board, inside the cabinet.
A number only means something once you know which display you are reading and which heater board sits behind it. So this guide starts with the controller, then sorts the numbers by what the heater was trying to do when it stopped. Each meaning comes from Bonaire’s own documents, which are named in the last sections. Where Bonaire does not publish a meaning, this page says so.
Bonaire heaters are made by Climate Technologies, which is the name printed on the Bonaire manuals and service sheets. For the wider picture of Bonaire products and manuals, see the Bonaire heating and cooling owner guide.
Which Bonaire controller do I have?
Look at the wall control first. Bonaire’s owner manuals describe two main controllers for ducted gas heaters, and each reports faults its own way.
The Navigator controller
The Navigator owner’s manual says the Navigator comes in two versions. One is wired and mounted in a cradle on the wall, with no batteries. The other is a wireless remote powered by three AAA batteries, with a battery icon for battery strength and a wave icon that shows when it is sending a command. The Navigator can run a gas heater, a Bonaire evaporative cooler and a Bonaire dual cycle refrigerated system. When it runs heating, the backlight glows orange.
The Navigator has eight buttons, including SETUP and ENTER. If your wall control has those two buttons and the Navigator name, read the Navigator reading steps and then the CO code groups.
The Slimline controller
The Slimline owner’s manual describes a slimmer control with five green LEDs and up and down buttons. Bonaire says the Slimline is only to be used with MB 3, 4 and 5 star heater controls and evaporative coolers. It runs one heater, one cooler, or one of each. If this is your control, go to the Slimline Er section.
No code on the wall, only a light on the heater
Every heater covered here has a status light on the main control board inside the heater cabinet. On MB4 and MB5 boards it is green. Bonaire’s board documents use its flash pattern to report faults. That light is for a technician to read, because the board sits behind the heater panels. The board flashes section explains what the patterns mean so you can follow what the technician tells you.
Find the heater model before you read any number
Bonaire’s Navigator manual says the model number, serial number and model description are on the appliance data plate on the end of the heater. Write them down or take a photo. The model tells a gasfitter which board generation you have, and the board generation decides which code list applies.
How do I read an error code on the Bonaire Navigator?
The Navigator stores faults in an error log, so you can read a code even after the screen has cleared. Bonaire’s Troubleshooting for Controllers sheet gives these steps for both the wired and the wireless Navigator.
- Turn the Navigator off. The error log only opens while the controller is off.
- Press and release the SETUP button.
- Move across the screen to the Advanced option and press ENTER. The word USER appears.
- Move to Erro and press ENTER.
- You now see appliance labels. Th is the thermostat, hE is the heater and EC is the evaporative cooler.
- Select hE for the heater and press ENTER.
- The bottom digits show the log number on the left and the error code on the right.
- Scroll through the ten entries in the log with the arrow buttons. Pressing the power button at any stage cancels the log.
Write down each code with its log number. A code that fills several log entries is a fault that keeps coming back, and that pattern is useful for the gasfitter. For a full tour of the buttons and screens, read the Bonaire Navigator manual guide.
What a Bonaire Navigator remote error can also mean
Not every Bonaire Navigator remote error comes from the heater. The Navigator manual says that if only one appliance is installed, pressing the heat and cool button shows “Error”. It also warns that the wireless remote should not sit near electrical equipment such as TVs and computers, and that devices such as wireless door bells or baby monitors can occasionally interfere. So check the label in the log first. A Th or EC label points away from the heater.
What do Bonaire Navigator CO codes mean?
Bonaire’s controller sheet confirms that the Navigator can show ERROR or CO on its screen, and it explains how to clear them. However, Bonaire’s owner documents do not print a table for the number that follows CO. No Bonaire Navigator error code list sits in the Navigator manual itself.
The numbered lists Bonaire does publish belong to the heater’s control board. The MB3 diagnostics sheet numbers its faults 1 to 12. The MB4 and MB5 diagnostics guide gives each fault an ERR code, from 13 up to 45. Neither document says in plain words that the number after CO is the same number. So a matching number is only a possible match, which Bonaire does not confirm. For that reason, give the gasfitter both the screen code and the log entry.
The groups below follow the order of Bonaire’s MB4 and MB5 table, from overheating to power, sensors, pressure switches, ignition, the gas valve and the board’s own safety checks.
Heater ran too hot: CO 1 and the overheat codes
If you are looking up a Bonaire heater CO 1 error, the heater generation matters. On the MB3 sheet, code 1 is “Overheat condition”, with the overheat switch reporting an overheat in progress or showing disconnected or open circuit. If your Navigator shows CO 1 on an MB3 heater, this is the possible match. MB3 code 7 is the over temperature lockout, after too many high limit activations.
The MB4 and MB5 guide has no code 1. Its overheat faults are code 20, an overheat lockout because the heater did not cool down in the allowed time, and code 21, an overheat lockout because the number of overheat events went past ten. Before a lockout, the board shows two short flashes during an overheat prevention cool down, which Bonaire says starts when duct temperature reaches 70°C.
For these faults, Bonaire’s guide tells technicians to check that the indoor fan is working, that the return air ductwork is not blocked, that static pressure is not too high and that the dampers are not all closed. Several of those start with things an owner can see.
- Clean the return air filter if your system has one. The Navigator manual says to clean it every 3 to 4 weeks in the heating season, and warns that a dirty filter can stop the heater on over temperature.
- Keep the return air grille clear. The manual says not to place articles in front of or over it.
- Check that enough outlets and zones are open on the controller.
If the overheat code returns after those checks, the cause sits in the fan, the ducts or the burner pressure. In other words, those are technician jobs.
Power reaching the heater: CO 15 and frequency faults
On the MB4 and MB5 guide, code 15 is a frequency check fault. If your Navigator shows CO 15, this is the possible match. The check of mains frequency failed at start up. Code 22 is the matching frequency lockout, where supply frequency is outside operating limits. On the MB3 sheet, code 8 is a frequency lockout with the same meaning.
Bonaire lists the checks for code 15 as a blown 240 volt fuse, a high voltage connection fault, electrical noise on the power supply or an internal control board problem. It also names solar power inverters, generators and battery backup power supplies as possible causes. If the code appeared while your home was running on a generator or backup supply, tell the technician.
The fuse, wiring and board are all inside the heater. The Navigator manual says only a qualified electrician should carry out electrical connections and maintenance, so leave the cabinet closed.
Duct temperature sensor: CO 17 and the thermistor codes
The heater has a temperature sensor, called a thermistor, in the outlet duct. On the MB4 and MB5 guide, code 17 is a thermistor lockout. The thermistor temperature failed to rise at the start of a heat cycle. Bonaire notes that from board software version 10 onwards this check runs every time the heater starts.
Two related codes follow. Code 18 means the thermistor reported below 20°C before start up. Bonaire’s first checks for it are whether the thermistor is installed in the outlet duct and plugged in correctly, or whether it is open circuit or faulty. Code 19 means the thermistor reported above 120°C before start up, which points to a short circuit or faulty sensor.
You cannot see the thermistor without going into the ducts or the heater. However, think back. If someone has recently worked in the roof space or under the floor near the heater, mention it, because a thermistor that is not in the outlet duct or not plugged in correctly is on Bonaire’s own check list.
Air pressure and flue: the pressure switch codes
Before the burner lights, a combustion fan clears the heat exchanger and pushes exhaust out through the flue. A pressure switch proves that this airflow is there. The MB4 and MB5 guide lists these lockouts.
- 23: primary pressure switch closed in the idle state.
- 24: secondary pressure switch closed in the idle state.
- 25: primary pressure switch did not close during pre purge.
- 26: primary pressure switch did not open after post purge.
- 27: secondary pressure switch did not open after post purge.
For code 25, Bonaire’s checks include a leaking heat exchanger, a blocked flue, a combustion fan running slowly or not at all, a wire off the switch, a leaking pressure tube or a faulty switch. A blocked or leaking flue is a carbon monoxide risk, so these codes are for a licensed gasfitter.
The owner’s part is limited to looking from the ground. The Navigator manual says the flue and cowl assembly should be clean and free of obstructions. Energy Safe Victoria’s page on heating your home with gas says to keep plants and animal nests away from the outdoor end of the flue. However, do not climb onto the roof or touch the flue.
Burner did not light: CO 30 and the ignition codes
On the MB4 and MB5 guide, code 30 is ignition lockout 1, the maximum number of re ignition attempts reached. If your Navigator shows CO 30, this is the possible match. Code 31 means the maximum number of unstable flame occurrences was reached. Code 32 means the flame was lost during heating too many times. Code 29 is a flame strength lockout, where flame strength readings are too low. On the MB3 sheet, code 5 is the ignition lockout, described as failure to ignite flame.
Bonaire’s technician checks for these codes cover the spark lead, the spark at the burner, the gas valve, gas pressure, the injectors and burners, the combustion fan and the flue. In short, all of those are gas work.
There is one owner check first. The Navigator manual says that if the gas supply is interrupted, the heater will try to relight and, if it cannot, it will lock out as part of its safety features, and it then needs a reset. So check whether other gas appliances in the home are working. If nothing has gas, the problem is the supply, not the heater. If only the heater is affected, reset it once and, if it locks out again, contact a licensed gasfitter.
Gas valve codes, including Bonaire Navigator error code 33
If your Navigator shows code 33, the MB4 and MB5 guide uses 33 for one of three gas valve faults. Bonaire does not confirm that the screen number is the board number, so treat this as a possible match.
- 33: modulation coil lockout. The gas valve modulation check failed, for example a disconnected or open circuit coil, or coil current too low.
- 34: modulation coil safety lockout. The check failed because of a short circuit or coil current too high.
- 35: main valve lockout. The board could not detect the main coil of the gas valve.
The gas valve controls the flow of gas to the burner. Switch the heater off at the Navigator and contact a licensed gasfitter. Do not reset these codes repeatedly.
Earth and safe start codes
The last group in the MB4 and MB5 guide covers the board’s own safety checks. Code 38 is a ground fault lockout for a poor earth connection to the chassis. Code 39 is a ground fault lockout where a flame was detected when no flame signal should be present. Codes 40 and 41 are safe start lockouts for false flame sensed in the idle state.
Codes 42 to 45 are safe start lockouts in the board’s safeguard checks, three of them timing faults and one a check that failed for an unknown reason. For each of those, Bonaire’s guide says the controller may have an internal fault. Earth faults and board faults are electrical and gas safety work, so these always need a technician.
Informational and condensate codes
Some entries are not breakdowns. Bonaire lists a forced post purge, where the heater runs a purge cycle after an incorrect sequence of events, as normal operation with no error code. Bonaire also lists, with no error code, a manual thermostat that was already calling for heat when power came on. Bonaire says this can happen after a power outage, and that turning the thermostat off then on clears it.
Two codes apply to MB4 and MB5 heaters only. Code 13 means the condensate level is too high, and on MB5 Bonaire’s first check is that the condensate drain is not blocked. Code 14 means the condensation sensor is open circuit. The drain and sensor connect inside the heater, so leave them to a technician.
Bonaire Navigator CO 55: not in the Bonaire documents used here
CO 55 is not listed in any of the five Bonaire documents used here: the MB3 sheet, the MB4 and MB5 guide, the Navigator manual, the controller sheet and the Slimline manual. So this page does not give it a meaning.
The safe next step is the same as for any unknown code. Note the code and the log entries, clear it once as the controller sheet describes, and watch the next start. If CO 55 comes back, leave the heater off and contact a licensed gasfitter. Tell them the heater model from the data plate. Also check the log label. If the fault sits under EC, it came from an evaporative cooler, not the heater.
What do Er codes on a Bonaire Slimline controller mean?
The Slimline owner’s manual says that while the Slimline is operating, an error is reported by “Er” on the screen. The controller stays in that state until the error is removed. To remove it, press and hold the up and down buttons together for five seconds, which sends a reset command to the appliance.
Bonaire’s controller sheet describes the same reset slightly differently. Press the up and down buttons together until CLD appears, then press the power button to start. It adds that switching the unit off and back on at the power also resets it.
Like the Navigator manual, the Slimline manual does not print a table of Er numbers. Because the Slimline only works with MB 3, 4 and 5 heater controls, the board lists above are the nearest Bonaire reference.
Bonaire Er5 error on a Slimline
None of the five Bonaire documents used here defines a Bonaire Er5 error. The MB3 sheet does list code 5 as an ignition lockout, failure to ignite flame, with the maximum number of re ignition or spark attempts reached. On an MB3 board that may be the match, but none of them links Er numbers to board codes.
Be careful with the number 5 on newer heaters. The MB4 and MB5 guide has no fault numbered 5. It does say that an MB5 board in normal idle shows five short flashes of its green light, and an MB4 shows four. So five flashes on an MB5 board is normal, not a fault.
So for Er5, check that other gas appliances have gas, clear the code once with the up and down buttons, and watch the next start. If the code returns, a licensed gasfitter needs to read the board and find the cause.
What do the flashing lights on a Bonaire heater board mean?
If you are looking up a Bonaire MB3 board flashing light code, these lights are on the control board inside the heater. Bonaire’s documents for both board types are written for service work, so treat this section as background for talking to a technician. Do not remove panels to see the board.
MB4 and MB5 boards: long and short pulses
The MB4 and MB5 guide says the green light shows controller status or a fault, and a red light that is on means the pressure switch contacts are closed. In idle, an MB5 board shows five short flashes and an MB4 board shows four. When the thermostat calls for heat, the board shows one short flash.
The guide says a long pulse always means the unit is in lockout. The number of long pulses gives the category, and the short pulses that follow give the cause.
- Short pulses only: normal operation and faults that are not lockouts.
- One long pulse: lockouts caused by external switches and sensors, such as the thermistor, over temperature switch, pressure switch or flame sensor.
- Two long pulses: lockouts caused by the unit’s hardware, ignition failure or the main gas valve.
- Three long pulses: safe start check faults or ground connection faults.
MB3 boards: numbered flash codes
The MB3 sheet describes a slow single flash as idle and waiting for a call for heat, and a slow double flash as normal operation with the thermostat closed. Its fault codes run from 1 to 12.
| MB3 code | Bonaire’s condition |
|---|---|
| 1 | Overheat condition |
| 2 | Pressure switch inactive |
| 3 | Purge or inter wait timer operating |
| 4 | Pressure switch lockout |
| 5 | Ignition lockout, failure to ignite flame |
| 6 | Gas valve fault lockout, valve detection failure |
| 7 | Over temperature lockout, high limit |
| 8 | Frequency lockout, timing fault |
| 9 | Flame lockout, invalid flame reading |
| 10 | Safe start lockout, false flame |
| 11 | Safe start lockout, secondary safeguard timing fault |
| 12 | Safe start lockout, safe start checks did not complete in time |
How do I reset a Bonaire Navigator error?
A Bonaire Navigator error reset is allowed, but only to give the heater one more try. Bonaire gives two ways to do it.
- The controller sheet says that if ERROR or CO shows on the screen, press ENTER once to clear it, then press the power button to start. Switching the unit off and back on also resets it.
- The Navigator manual’s problem solving chart says to turn the unit off for more than two seconds, then on again, to reset it. If it still does not start, it says to call for service.
The Navigator manual also notes that if power is interrupted during heating, the controls automatically turn off the gas. Depending on the unit, it may not restart when power returns, and the controller then needs a manual reset.
When to stop resetting
A lockout is a safety stop. If the same code comes back after one reset, stop and leave the heater off. Repeated resets do not fix a blocked flue, a failing gas valve or a faulty board, and they can hide what the log would otherwise show. For symptoms that do not come with a code, such as weak airflow or a heater that will not start, see Bonaire ducted heating troubleshooting.
Which Bonaire codes need a licensed gasfitter?
Gas work on a ducted heater is not an owner job. Energy Safe Victoria says gas work is not a DIY project and that homeowners must always use a licensed or registered gasfitter. Other states and territories have their own gas regulator, so check its rules. Leave the heater off and contact a licensed gasfitter for any of these.
- Any pressure switch or flue code, from 23 to 27.
- Any ignition or flame code, including 29 to 32.
- Any gas valve code, from 33 to 35.
- Any earth or safe start code, from 38 to 45.
- An overheat code that returns after you have cleaned the filter and opened the outlets.
- Any code that comes back after one reset, or a code you cannot match.
If you smell gas or feel unwell
Energy Safe Victoria’s gas emergency page says to turn off the gas at the meter, or at the tank or cylinder for LP gas, only if it is safe to do so. Put out all flames, do not operate electrical switches or devices, open doors and windows, and keep people away. Then call your gas distributor, using the contact details on your gas bill.
The Better Health Channel lists carbon monoxide symptoms that include headaches, dizziness, nausea, tiredness and shortness of breath. If you suspect carbon monoxide, it says to open windows and doors, turn off the appliance and go outside to breathe fresh air. Call triple zero in an emergency, see your GP about any symptoms and have the heater serviced before you use it again. Read more on carbon monoxide and gas heaters.
Servicing between faults
The Navigator manual says a Bonaire ducted gas heater should be serviced annually by a qualified and licensed service technician, with gas pressures, the flue, fans, ignition and burners checked each year. Energy Safe Victoria’s general advice is a service at least once every two years by a qualified gasfitter. Follow the manual for your heater, since it is the stricter of the two. For a plain guide to the visit, read what a ducted heating service covers.
Where can I find the Bonaire error code list PDF?
Bonaire’s download documents page, listed as Technical Manuals under Support on bonaire.com.au, holds product and installation manuals. These are the Bonaire files this page uses, all served from bonaire.com.au.
- Navigator Controller owner’s manual, for the controller, reset steps and heater maintenance.
- Troubleshooting for Controllers, for the error log steps and the Navigator and Slimline resets.
- MB series control board diagnostics, the MB4 and MB5 fault list.
- MB3 diagnostics fault codes, the MB3 list.
Treat any Bonaire error code list PDF from another website with care. Bonaire has built several heater generations, and the same number means different things on different boards.
Do Bonaire evaporative coolers use the same codes?
No. The Navigator error log keeps cooler faults under the EC label, separate from heater faults under hE. A Bonaire cooler uses its own list, so a number that means one thing on the heater can mean something else on the cooler. Never read a cooler code against a heater list. For cooler faults, read the Bonaire evaporative cooler error log guide.
What should I do first when a Bonaire code appears?
Bonaire error codes make sense in four steps. Identify the controller. Read the log and note the hE number. Match it to your heater’s board list using the model on the data plate. Then follow the safe checks: filter, return air grille, open outlets and gas supply. Reset once only. Anything involving the flue, gas valve, ignition, earth or board needs a licensed gasfitter.